Guideline B-08
This type of vessel is classified according to Table 4, provided the gas is being continuously removed. Examples of such vessels are domestic warm water vessels, where entering air is accumulated on the top, and is normally being removed by operation.
Guideline B-17
The guiding factor should be based on the characteristic of the pressure accessory. In some cases both volume and DN are considered appropriate. In such cases, the pressure accessory must be classified in the highest category. In the case of valves, DN is normally the more appropriate. Reason:It should be noted that some linguistic versions […]
Guideline B-41
As of 1 June 2015 classification of fluids is based on article 13 of PED 2014/68/EU. Article 13 paragraph 1 (a) lists the physical and health hazard classes and categories for substances and mixtures included in Group 1. The classification is based on the CLP Regulation (EC) No 1272/2008. The table below provides an overview […]